FIRE RESISTANT CABLES, NON ARMOURED CABLES

Specifications

Conductor                           : Plain Annealed Copper Conductor, Class 2
Fire Proof Layer                   : MGT-Glass Tapes
Insulation                             : A) Mineral-Filled XLPO-LSZH (XLEVA) Or                                                                                                                       B) XLPE Or                                                                                                                                                                             C) PVC

Colour of Insulation           : 2 Cores – Red And Black or (Brown And Blue)                                                                                                             3 Cores – Red, Yellow And Blue or (Brown, Black And Grey)                                                                                     4 Cores – Red, Yellow, Blue And Black or (Brown, Black, Grey And Blue)                                                               5 Cores – Red, Yellow, Blue, Black And Green or (Brown, Black, Grey, Blue And Green/Yellow)

Fillers                                     : PP Yarn (Optional)
Core Wrapping                   : Flame Retardant Tapes or Polyester Tape (Optional)
Sheath                                  : A) Mineral-Filled LSZH (Low Smoke Zero Halogen) or                                                                                               B) PVC-FR (Flame Retardant PVC)

Colour Sheath                     : Orange or Other Colour
Applicable Standards       : IEC60502-1, IEC60331-21, BS7846 CAT.F2, IEC60332-3-22 CAT.A, IEC60332-3-23 CAT.B & IEC60332-3-24 CAT.C

Voltage                                 : 600/1000 Volts

SPEC                                     :

              • CU/MGT/XLPO-LSZH(FR-MI)
              • CU/MGT/XLPE/LSZH
              • CU/MGT/XLPE/PVC-FR
              • CU/MGT/PVC/PVC-FR

2 Cores

Nominal Cross Sectional Area of Conductor (mm2)Max Conductor Resistance at 20degree celsius (ohm//km)Thickness of InsulationThickness of Sheath (mm)Approx. Overall Diameter (mm)Approx. Net Weight (kg/km)
1.512.10.71.811.2176
2.57.410.71.812.0210
44.610.71.813.0263
63.080.71.814.4329
101.830.71.816.0410
161.150.71.818.0570
250.7270.91.821.0831
350.5240.91.823.21082
500.3871.01.825.61399
700.2681.11.829.51908
950.1931.12.032.82570
1200.1531.22.137.63179
1500.1241.42.241.43878
1850.09911.62.346.04808
2400.07541.72.551.46220
3000.06011.82.756.67679
4000.04702.02.964.09768

3 Cores

Nominal Cross Sectional Area of Conductor (mm2)Max Conductor Resistance at 20degree celsius (ohm//km)Thickness of InsulationThickness of Sheath (mm)Approx. Overall Diameter (mm)Approx. Net Weight (kg/km)
1.512.10.71.811.8196
2.57.410.71.812.6243
44.610.71.813.7311
63.080.71.815.2400
101.830.71.816.9510
161.150.71.819.1717
250.7270.91.822.31052
350.5240.91.824.71380
500.3871.01.827.31874
700.2681.11.931.52612
950.1931.12.035.13480
1200.1531.22.140.24340
1500.1241.42.344.35335
1850.09911.62.449.36629
2400.07541.72.655.18574
3000.06011.82.860.710640
4000.04702.03.168.713460

4 Cores

Nominal Cross Sectional Area of Conductor (mm2)Max Conductor Resistance at 20degree celsius (ohm//km)Thickness of InsulationThickness of Sheath (mm)Approx. Overall Diameter (mm)Approx. Net Weight (kg/km)
1.512.10.71.812.7229
2.57.410.71.813.7288
44.610.71.814.9375
63.080.71.816.6486
101.830.71.818.6645
161.150.71.821.0915
250.7270.91.824.61354
350.5240.91.827.31769
500.3871.01.830.22315
700.2681.11.934.93295
950.1931.12.038.84592
1200.1531.22.144.65710
1500.1241.42.349.16925
1850.09911.62.454.78714
2400.07541.72.661.111249
3000.06011.82.867.414000
4000.04702.03.176.217801